AC Input
Voltage: 187 VAC to 264 VAC (nominal)
Frequency 45 Hz to 65 Hz
Maximum Current 12 A
Power Factor &gt.0.99 from 50 to 100% load
Protection:
High and low voltage protection, surge and lightning protection Adapts to poor quality grid (voltage dip, weak mains) Disconnection at 415 VAC Mains fuses in both lines
DC Output
Voltage -42 VDC to -58 VDC
Maximum Power 2000 W
Maximum Current 42 A @ -48 VDC, limit set point 0 to 42 A (see figure 2)
Peak Efficiency 96.2%
Protection Fuse for reverse connection and back feeding protection High voltage shutdown High temperature protection
Adjuntos: